C200HG-CPU43 communication
C200HG-CPU43 of a OFF in the
PLC-DIP5 state, can not communicate with the PC, whether there are other reasons? Thank you
DIP5 needet C200HG-CPU43 ON C200HG-CPU43 can use the default settings and computer connections. Because DIP5 dial to ON is the use of PC connection communication, only in this way and the computer connection to try.