C200H forn CQM1-CIFO2 of CQM1-CIFO2PLC and computer communication. I use COM1-CIFO2 line of communication, unable to communicate with the computer form. Request master!!!!
Re: Time:2016-7-12 15:39:00
Is it C200H-CPU or C200HE/X/G, which directly correspond in CQM1-CIF02.
Re:Re: Time:2016-7-12 18:03:00
If it is C200H-CPU need to add C200H-LK201-V1+XW2Z-200P-V to computer communications.