Home >> Technical Problems >> How many pulses can be output of FX1S-14MR
Catalogue

How many pulses can be output of FX1S-14MR

Time:2016-2-29 3:51:38

How many s FX1S-14MR can FX1S-14MR be output of FX1S-14MR?can use PLSY instructions
Re:  Time:2016-2-29 15:31:00
FX1S-14MR is the output of the relay, relay output type can not output pulse, can not use PLSY.
Re:Re:  Time:2016-2-29 17:55:00
Switch to FX1S-14MT-001;
Re:Re:Re:  Time:2016-2-29 22:43:00
Yes, transistor output type of the output pulse, high frequency 100KHz, 2 pulseoutputs.