MR-JE to
MR-JE CN1, CN2
motor line power cord alarm on the street whatAL.16.3 will not work, replaced for servo drives is still the same, reading theinstructions is to set the manual is to set up a 2-wire/4-wire how to set up for expert advice
Hello, AL MR-JE is MR-JE an encoder exception, there may be a cable problem, there arelikely to be coder problem, if it is 2/4 wire set reason, long distance encodercables need to set PC22=1***.