Use the Qes Q64A-GH 02H Q64A-GH CPU, Q64AD-GH modules do not know how to set the selection of 32-bit resolution, the default is 16-bit
Re:  Time:2016-6-20 16:15:00
Q64AD-GH does not need to adjust the resolution, because the buffer that stores digital output values are divided into 16-bit and 32-bit 2, requires 0-32000 range of 16-bit data to view the data buffer BH CH DH EH, if you need to 0-64000 range of 32-bitdata 36H-3DH data can be viewed.