Home >> Products >> 77
ABB Inverter ACS800-01-0016-5
Product Name: Inverter.
Model: ACS800-01-0016-5.
UN = 500 V (Range 380 to 500 V). The power ratings are valid at nominal voltage 500 V.
Rated current available continuously without overloadability at 40 °C: 19A.
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd: 24A.
Frame size: R3.
Continuous current allowing 110% IN for 1 min / 5 min at 40 °C: 18A.
Typical motor power in light-overload use: 11Kw.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C: 13A.
Typical motor power in heavy-duty use: 7.5KW.
Typical motor power in no-overload use: 11KW
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
In -0205-3 and -0255-5 units, H1 is 994 mm, depth 424 mm and weight is 80 kg.
ABB Inverter ACS800-01-0060-5
Product Name: Inverter.
Model: ACS800-01-0060-5.
UN = 500 V (Range 380 to 500 V). The power ratings are valid at nominal voltage 500 V.
Rated current available continuously without overloadability at 40 °C: 79A.
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd: 112A.
Typical motor power in no-overload use: 45KW
Frame size: R5.
Typical motor power in light-overload use: 45Kw.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C: 60A.
Typical motor power in heavy-duty use: 37KW.
Continuous current allowing 110% IN for 1 min / 5 min at 40 °C: 75A.
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
In -0205-3 and -0255-5 units, H1 is 994 mm, depth 424 mm and weight is 80 kg.
ABB Inverter ACS800-01-0005-2
Product Name: Inverter.
Model: ACS800-01-0005-2.
UN = 230 V (Range 208 to 240 V). The power ratings are valid at nominal voltage 230 V.
Rated current available continuously without overloadability at 40 °C: 13.9A
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd: 17.6A.
Typical motor power in no-overload use: 3KW
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
Typical motor power in light-overload use: 3Kw.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C: 9.3A.
Typical motor power in heavy-duty use: 2.2KW.
Frame size: R2.
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
Continuous current allowing 110% IN for 1 min / 5 min at 40 °C: 12.7A.
In -0205-3 and -0255-5 units, H1 is 994 mm, depth 424 mm and weight is 80 kg.
ABB Inverter ACS800-01-0006-2
Product Name: Inverter.
Model: ACS800-01-0006-2.
UN = 230 V (Range 208 to 240 V). The power ratings are valid at nominal voltage 230 V.
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd: 24A.
Typical motor power in no-overload use: 4KW
Continuous current allowing 110% IN for 1 min / 5 min at 40 °C: 18A.
Typical motor power in light-overload use: 4Kw.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C: 14A.
Typical motor power in heavy-duty use: 3KW.
Frame size: R3.
Rated current available continuously without overloadability at 40 °C: 19A
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
In -0205-3 and -0255-5 units, H1 is 994 mm, depth 424 mm and weight is 80 kg.
ABB Inverter ACS800-01-0003-2
Product Name: Inverter.
Model: ACS800-01-0003-2.
UN = 230 V (Range 208 to 240 V). The power ratings are valid at nominal voltage 230 V.
Rated current available continuously without overloadability at 40 °C: 8.5A
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd: 10.8A.
Typical motor power in no-overload use: 1.5KW
Continuous current allowing 110% IN for 1 min / 5 min at 40 °C: 7.7A.
Typical motor power in light-overload use: 1.5Kw.
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
Typical motor power in heavy-duty use: 1.1KW.
Frame size: R2.
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C: 5.7A.
In -0205-3 and -0255-5 units, H1 is 994 mm, depth 424 mm and weight is 80 kg.
ABB Inverter ACS800-01-0025-2
Product Name: Inverter.
Model: ACS800-01-0025-2.
UN = 230 V (Range 208 to 240 V). The power ratings are valid at nominal voltage 230 V.
Rated current available continuously without overloadability at 40 °C: 72A
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd: 86A.
Typical motor power in no-overload use: 18.5KW
Continuous current allowing 110% IN for 1 min / 5 min at 40 °C: 69A.
Typical motor power in light-overload use: 18.5Kw.
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
Typical motor power in heavy-duty use: 11KW.
Frame size: R5.
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C: 49A.
In -0205-3 and -0255-5 units, H1 is 994 mm, depth 424 mm and weight is 80 kg.
ABB Inverter ACS800-01-0030-2
Product Name: Inverter.
Model: ACS800-01-0030-2.
UN = 230 V (Range 208 to 240 V). The power ratings are valid at nominal voltage 230 V.
Rated current available continuously without overloadability at 40 °C: 86A
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Typical motor power in heavy-duty use: 15KW.
Typical motor power in no-overload use: 22KW
Continuous current allowing 110% IN for 1 min / 5 min at 40 °C: 80A.
Typical motor power in light-overload use: 22Kw.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C: 60A.
Phd: 112A.
Frame size: R5.
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
In -0205-3 and -0255-5 units, H1 is 994 mm, depth 424 mm and weight is 80 kg.
ABB Inverter ACS800-01-0040-2
Product Name: Inverter.
Model: ACS800-01-0040-2.
UN = 230 V (Range 208 to 240 V). The power ratings are valid at nominal voltage 230 V.
Rated current available continuously without overloadability at 40 °C: 103A
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd: 138A.
Typical motor power in no-overload use: 30KW
Continuous current allowing 110% IN for 1 min / 5 min at 40 °C: 94A.
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C: 69A.
Typical motor power in heavy-duty use: 18.5KW.
Frame size: R5.
Typical motor power in light-overload use: 22Kw.
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
In -0205-3 and -0255-5 units, H1 is 994 mm, depth 424 mm and weight is 80 kg.
163 Results 12/Page Page 10 of 14     [First Page] << Previous 6 7 8 9 10 11 12 13 14 Next >>