Product Name: Inverter.
Model:
ACS800-01-0140-5.
UN ABB ACS800-01-0165-3 = 500 V (Range 380 to 500 V). The power ratings are valid ABB ACS800-01-0165-3 at nominal voltage 500 V.
Rated current available continuously without overloadability ABB ACS800-01-0165-3 at 40 °C: 180A.
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd: 282A.
Frame size: R6.
Continuous current allowing 110% IN for 1 min / 5 min at 40 °C: 163A.
Typical motor power in light-overload use: 110Kw.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C: 141A.
Typical motor power in heavy-duty use: 90KW.
Typical motor power in no-overload use: 110KW
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
In -0205-3 and -0255-5 units, H1 is 994 mm, depth 424 mm and weight is 80 kg.
Product Name: Inverter.
Model: ACS800-01-0165-5.
UN = 500 V (Range 380 to 500 V). The power ratings are valid at nominal voltage 500 V.
Rated current available continuously without overloadability at 40 °C: 225A.
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd: 326A.
Typical motor power in no-overload use: 132KW
Continuous current allowing 110% IN for 1 min / 5 min at 40 °C: 220A.
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C: 163A.
Typical motor power in heavy-duty use: 110KW.
Frame size: R6.
Typical motor power in light-overload use: 132Kw.
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
In -0205-3 and -0255-5 units, H1 is 994 mm, depth 424 mm and weight is 80 kg.
Product Name: Inverter.
Model: ACS800-01-0120-7.
UN = 690 V (Range 525 to 690 V). The power ratings are valid at nominal voltage 690 V.
Rated current available continuously without overloadability at 40 °C: 113A.
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd: 172A.
Typical motor power in no-overload use: 110KW
Frame size: R6.
Typical motor power in light-overload use: 90Kw.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C: 86A.
Typical motor power in heavy-duty use: 75KW.
Continuous current allowing 110% IN for 1 min / 5 min at 40 °C: 108A.
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
In -0205-3 and -0255-5 units, H1 is 994 mm, depth 424 mm and weight is 80 kg.
Product Name: Inverter.
Model: ACS800-01-0100-3.
UN = 400 V (Range 380 to 415 V). The power ratings are valid at nominal voltage 400 V.
Rated current available continuously without overloadability at 40 °C: 166A.
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd: 202A.
Typical motor power in no-overload use: 90KW
Continuous current allowing 110% IN for 1 min / 5 min at 40 °C: 155A.
Typical motor power in light-overload use: 75Kw.
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
Typical motor power in heavy-duty use: 55KW.
Frame size: R6.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C: 115A.
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
In -0205-3 and -0255-5 uniits, ACS800-01-0165-3 H1 is 994 mm, depth 424 mm and weight is 80 kg.
...More Related Model
>>>>