Home >> Products >> ACS800-01-0025-
ABB Inverter ACS800-01-0025-7
Product Name: Inverter.
Model: ACS800-01-0025-7.
UN = 690 V (Range 525 to 690 V). The power ratings are valid at nominal voltage 690 V.
Rated current available continuously without overloadability at 40 °C: 25A.
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd: 38A.
Typical motor power in no-overload use: 22KW
Frame size: R4.
Typical motor power in light-overload use: 18.5Kw.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C: 19A.
Typical motor power in heavy-duty use: 15KW.
Continuous current allowing 110% IN for 1 min / 5 min at 40 °C: 23A.
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
In -0205-3 and -0255-5 units, H1 is 994 mm, depth 424 mm and weight is 80 kg.
ABB Inverter ACS800-01-0025-3
Product Name: Inverter.
Model: ACS800-01-0025-3.
UN = 400 V (Range 380 to 415 V). The power ratings are valid at nominal voltage 400 V.
Rated current available continuously without overloadability at 40 °C: 44A.
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd: 62A.
Frame size: R4.
Continuous current allowing 110% IN for 1 min / 5 min at 40 °C: 41A.
Typical motor power in light-overload use: 18.5Kw.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C: 32A.
Typical motor power in heavy-duty use: 15KW.
Typical motor power in no-overload use: 22KW
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
In -0205-3 and -0255-5 units, H1 is 994 mm, depth 424 mm and weight is 80 kg.
ABB Inverter ACS800-01-0025-2
Product Name: Inverter.
Model: ACS800-01-0025-2.
UN = 230 V (Range 208 to 240 V). The power ratings are valid at nominal voltage 230 V.
Rated current available continuously without overloadability at 40 °C: 72A
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd: 86A.
Typical motor power in no-overload use: 18.5KW
Continuous current allowing 110% IN for 1 min / 5 min at 40 °C: 69A.
Typical motor power in light-overload use: 18.5Kw.
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
Typical motor power in heavy-duty use: 11KW.
Frame size: R5.
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C: 49A.
In -0205-3 and -0255-5 units, H1 is 994 mm, depth 424 mm and weight is 80 kg.
4 Results 12/Page Page 1 of 1