Product Name: Inverter.
Model:
ACS800-01-0025-5.
UN ABB ACS800-01-0025-7 = 500 V (Range 380 to 500 V). The power ratings are valid ABB ACS800-01-0025-7 at nominal voltage 500 V.
Rated current available continuously without overloadability ABB ACS800-01-0025-7 at 40 掳C: 34A.
Maximum output current. Available for 10 s at Inverter start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd: 46A.
Typical Inverter motor power in no-overload use: 18.5KW
Continuous current allowing 110% IN Inverter for 1 min / 5 min at 40 掳C: 31A.
Typical motor power in light-overload use: 18.5Kw.
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
Typical motor power in heavy-duty use: 15KW.
Frame size: R3.
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 掳C: 23A.
In -0205-3 and -0255-5 units, H1 is 994 mm, depth 424 mm and weight is 80 kg.
Product Name: Inverter.
Model: ACS800-01-0025-3.
UN = 400 V (Range 380 to 415 V). The power ratings are valid at nominal voltage 400 V.
Rated current available continuously without overloadability at 40 掳C: 44A.
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd: 62A.
Frame size: R4.
Continuous current allowing 110% IN for 1 min / 5 min at 40 掳C: 41A.
Typical motor power in light-overload use: 18.5Kw.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 掳C: 32A.
Typical motor power in heavy-duty use: 15KW.
Typical motor power in no-overload use: 22KW
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
In -0205-3 and -0255-5 units, H1 is 994 mm, depth 424 mm and weight is 80 kg.
Product Name: Inverter.
Model: ACS800-01-0025-2.
UN = 230 V (Range 208 to 240 V). The power ratings are valid at nominal voltage 230 V.
Rated current available continuously without overloadability at 40 掳C: 72A
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd: 86A.
Typical motor power in no-overload use: 18.5KW
Continuous current allowing 110% IN for 1 min / 5 min at 40 掳C: 69A.
Typical motor power in light-overload use: 18.5Kw.
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
Typical motor power in heavy-duty use: 11KW.
Frame size: R5.
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 掳C: 49A.
In -0205-3 and -0255-5 uunits, ABB ACS800-01-0025-7 H1 is 994 mm, depth 424 mm and weight is 80 kg.