Product Name: Inverter.
Model: ACS800-01-0120-3.
UN = 400 V (Range 380 to 415 V). The power ratings are valid at nominal voltage 400 V.
Rated current available continuously without overloadability at 40 °C: 202A.
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd: 282A.
Typical motor power in no-overload use: 110KW
Frame size: R6.
Typical motor power in light-overload use: 90Kw.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C: 141A.
Typical motor power in heavy-duty use: 75KW.
Continuous current allowing 110% IN for 1 min / 5 min at 40 °C: 184A.
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
In -0205-3 and -0255-5 units, H1 is 994 mm, depth 424 mm and weight is 80 kg.
Product Name: Inverter.
Model: ACS800-01-0165-3.
UN = 400 V (Range 380 to 415 V). The power ratings are valid at nominal voltage 400 V.
Rated current available continuously without overloadability at 40 °C: 260A.
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd: 326A.
Typical motor power in no-overload use: 132KW
Continuous current allowing 110% IN for 1 min / 5 min at 40 °C: 254A.
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C: 215A.
Typical motor power in heavy-duty use: 110KW.
Frame size: R6.
Typical motor power in light-overload use: 132Kw.
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
In -0205-3 and -0255-5 units, H1 is 994 mm, depth 424 mm and weight is 80 kg.
Product Name: Inverter.
Model: ACS800-01-0011-5.
UN = 500 V (Range 380 to 500 V). The power ratings are valid at nominal voltage 500 V.
Frame size: R2.
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd: 17.6A.
Typical motor power in no-overload use: 7.5KW
Continuous current allowing 110% IN for 1 min / 5 min at 40 °C: 12A.
Typical motor power in light-overload use: 7.5Kw.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C: 9.2A.
Typical motor power in heavy-duty use: 5.5KW.
Rated current available continuously without overloadability at 40 °C: 13.2A.
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
In -0205-3 and -0255-5 units, H1 is 994 mm, depth 424 mm and weight is 80 kg.
Product Name: Inverter.
Model: ACS800-01-0025-5.
UN = 500 V (Range 380 to 500 V). The power ratings are valid at nominal voltage 500 V.
Rated current available continuously without overloadability at 40 °C: 34A.
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd: 46A.
Typical motor power in no-overload use: 18.5KW
Continuous current allowing 110% IN for 1 min / 5 min at 40 °C: 31A.
Typical motor power in light-overload use: 18.5Kw.
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
Typical motor power in heavy-duty use: 15KW.
Frame size: R3.
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C: 23A.
In -0205-3 and -0255-5 units, H1 is 994 mm, depth 424 mm and weight is 80 kg.