Home >> Products >> All Products
ABB Inverter ACS800-01-0070-5
Product Name: Inverter.
Model: ACS800-01-0070-5.
UN = 500 V (Range 380 to 500 V). The power ratings are valid at nominal voltage 500 V.
Rated current available continuously without overloadability at 40 °C: 96A.
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd: 138A.
Typical motor power in heavy-duty use: 45KW.
Continuous current allowing 110% IN for 1 min / 5 min at 40 °C: 88A.
Typical motor power in light-overload use: 55Kw.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C: 69A.
Typical motor power in no-overload use: 55KW
Frame size: R5.
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
In -0205-3 and -0255-5 units, H1 is 994 mm, depth 424 mm and weight is 80 kg.
ABB Inverter ACS800-01-0105-5
Product Name: Inverter.
Model: ACS800-01-0105-5.
UN = 500 V (Range 380 to 500 V). The power ratings are valid at nominal voltage 500 V.
Rated current available continuously without overloadability at 40 °C: 145A.
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd: 170A.
Typical motor power in no-overload use: 90KW
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
Typical motor power in light-overload use: 90Kw.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C: 100A.
Typical motor power in heavy-duty use: 55KW.
Frame size: R5.
Continuous current allowing 110% IN for 1 min / 5 min at 40 °C: 141A.
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
In -0205-3 and -0255-5 units, H1 is 994 mm, depth 424 mm and weight is 80 kg.
ABB Inverter ACS800-01-0120-5
Product Name: Inverter.
Model: ACS800-01-0120-5.
UN = 500 V (Range 380 to 500 V). The power ratings are valid at nominal voltage 500 V.
Rated current available continuously without overloadability at 40 °C: 157A.
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd: 202A.
Typical motor power in no-overload use: 90KW
Continuous current allowing 110% IN for 1 min / 5 min at 40 °C: 145A.
Frame size: R6.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C: 113A.
Typical motor power in heavy-duty use: 75KW.
Typical motor power in light-overload use: 90Kw.
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
In -0205-3 and -0255-5 units, H1 is 994 mm, depth 424 mm and weight is 80 kg.
ABB Inverter ACS800-01-0140-5
Product Name: Inverter.
Model: ACS800-01-0140-5.
UN = 500 V (Range 380 to 500 V). The power ratings are valid at nominal voltage 500 V.
Rated current available continuously without overloadability at 40 °C: 180A.
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd: 282A.
Frame size: R6.
Continuous current allowing 110% IN for 1 min / 5 min at 40 °C: 163A.
Typical motor power in light-overload use: 110Kw.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C: 141A.
Typical motor power in heavy-duty use: 90KW.
Typical motor power in no-overload use: 110KW
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
In -0205-3 and -0255-5 units, H1 is 994 mm, depth 424 mm and weight is 80 kg.
ABB Inverter ACS800-01-0165-5
Product Name: Inverter.
Model: ACS800-01-0165-5.
UN = 500 V (Range 380 to 500 V). The power ratings are valid at nominal voltage 500 V.
Rated current available continuously without overloadability at 40 °C: 225A.
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd: 326A.
Typical motor power in no-overload use: 132KW
Continuous current allowing 110% IN for 1 min / 5 min at 40 °C: 220A.
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C: 163A.
Typical motor power in heavy-duty use: 110KW.
Frame size: R6.
Typical motor power in light-overload use: 132Kw.
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
In -0205-3 and -0255-5 units, H1 is 994 mm, depth 424 mm and weight is 80 kg.
ABB Inverter ACS800-01-0205-5
Product Name: Inverter.
Model: ACS800-01-0205-5.
UN = 500 V (Range 380 to 500 V). The power ratings are valid at nominal voltage 500 V.
Rated current available continuously without overloadability at 40 °C: 260A.
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd: 326A.
Typical motor power in no-overload use: 160KW
Frame size: R6.
Typical motor power in light-overload use: 160Kw.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C: 215A.
Typical motor power in heavy-duty use: 132KW.
Continuous current allowing 110% IN for 1 min / 5 min at 40 °C: 254A.
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
In -0205-3 and -0255-5 units, H1 is 994 mm, depth 424 mm and weight is 80 kg.
ABB Inverter ACS800-01-0255-5
Product Name: Inverter.
Model: ACS800-01-0255-5.
UN = 500 V (Range 380 to 500 V). The power ratings are valid at nominal voltage 500 V.
Rated current available continuously without overloadability at 40 °C: 290A.
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd: 351A.
Typical motor power in no-overload use: 200KW
Frame size: R6.
Typical motor power in light-overload use: 200Kw.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C: 234A.
Typical motor power in heavy-duty use: 160KW.
Continuous current allowing 110% IN for 1 min / 5 min at 40 °C: 285A.
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
In -0205-3 and -0255-5 units, H1 is 994 mm, depth 424 mm and weight is 80 kg.
ABB Inverter ACS800-01-0011-7
Product Name: Inverter.
Model: ACS800-01-0011-7.
UN = 690 V (Range 525 to 690 V). The power ratings are valid at nominal voltage 690 V.
Rated current available continuously without overloadability at 40 °C: 13A.
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd: 14A.
Typical motor power in no-overload use: 11KW
Continuous current allowing 110% IN for 1 min / 5 min at 40 °C: 11.5A.
Frame size: R4.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C: 8.5A.
Typical motor power in heavy-duty use: 5.5KW.
Typical motor power in light-overload use: 7.5Kw.
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
In -0205-3 and -0255-5 units, H1 is 994 mm, depth 424 mm and weight is 80 kg.
ABB Inverter ACS800-01-0016-7
Product Name: Inverter.
Model: ACS800-01-0016-7.
UN = 690 V (Range 525 to 690 V). The power ratings are valid at nominal voltage 690 V.
Rated current available continuously without overloadability at 40 °C: 17A.
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd: 19A.
Typical motor power in no-overload use: 15KW
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
Typical motor power in light-overload use: 11Kw.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C: 11A.
Typical motor power in heavy-duty use: 7.5KW.
Frame size: R4.
Continuous current allowing 110% IN for 1 min / 5 min at 40 °C: 15A.
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
In -0205-3 and -0255-5 units, H1 is 994 mm, depth 424 mm and weight is 80 kg.
ABB Inverter ACS800-01-0020-7
Product Name: Inverter.
Model: ACS800-01-0020-7.
UN = 690 V (Range 525 to 690 V). The power ratings are valid at nominal voltage 690 V.
Rated current available continuously without overloadability at 40 °C: 22A.
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd: 28A.
Typical motor power in no-overload use: 18.5KW
Continuous current allowing 110% IN for 1 min / 5 min at 40 °C: 20A.
Typical motor power in light-overload use: 15Kw.
Frame size: R4.
Typical motor power in heavy-duty use: 11KW.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C: 15A.
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
In -0205-3 and -0255-5 units, H1 is 994 mm, depth 424 mm and weight is 80 kg.
ABB Inverter ACS800-01-0025-7
Product Name: Inverter.
Model: ACS800-01-0025-7.
UN = 690 V (Range 525 to 690 V). The power ratings are valid at nominal voltage 690 V.
Rated current available continuously without overloadability at 40 °C: 25A.
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd: 38A.
Typical motor power in no-overload use: 22KW
Frame size: R4.
Typical motor power in light-overload use: 18.5Kw.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C: 19A.
Typical motor power in heavy-duty use: 15KW.
Continuous current allowing 110% IN for 1 min / 5 min at 40 °C: 23A.
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
In -0205-3 and -0255-5 units, H1 is 994 mm, depth 424 mm and weight is 80 kg.
ABB Inverter ACS800-01-0030-7

Product Name: Inverter.
Model: ACS800-01-0030-7.
UN = 690 V (Range 525 to 690 V). The power ratings are valid at nominal voltage 690 V.
Rated current available continuously without overloadability at 40 °C: 33A.
Maximum output current. Available for 10 s at start, otherwise as long as allowed by drive temperature. Note: max. motor shaft power is 150% Phd: 44A.
Typical motor power in no-overload use: 30KW
Continuous current allowing 110% IN for 1 min / 5 min at 40 °C: 30A.
Frame size: R4.
Continuous current allowing 150% Ihd for 1 min / 5 min at 40 °C: 22A.
Typical motor power in heavy-duty use: 18.5KW.
Typical motor power in light-overload use: 22Kw.
ACS800-01 without cable connection box does not ful? ll IP21 requirements.
In -0205-3 and -0255-5 units, H1 is 977 mm and weight is 70 kg.
In -0205-3 and -0255-5 units, H1 is 994 mm, depth 424 mm and weight is 80 kg.

14193 Results 12/Page Page 313 of 1183     [First Page] << Previous 309 310 311 312 313 314 315 316 317 318 Next >> [Last Page]